Pressure control P100AP-3D Johnson Control
Low-pressure capsule pressure switch for direct installation - is characterized by small dimensions and fixed settings. Factory-set values are not subject to user adjustment - therefore, the appropriate pressure switch model should be selected for the specific requirements of the protected installation. The pressure switch is designed for direct installation on the refrigeration pipeline and does not require additional mounting brackets.
The main application of this type of pressure switch is switching on/off condenser fans, but it can also control the operation of other executive elements. P100 series pressure switches can be used for all non-corrosive refrigerants, such as: R134a, R32, R404, R410A R290 (Propane), R600, R1234, R744 (CO2) and others.
Features:
- Compact design and low weight
- Contact opening at pressure: 10.34 bar
- Contact closing at pressure: 15.51 bar
- Pressure connection: ¼” SAE internal thread
- Automatic reset
- Length of electrical cables: 1.2mb
- Hermetic, dust-proof housing, IP67
Application:
- Air conditioning of computer rooms
- Condensers of refrigeration/air conditioning systems
- Commercial refrigeration
- Ice machines
- Food storage devices